High Capacity Water Heaters - Performance
Performance Data For Multiple Installations At Varying Temperatures
The performance of these heaters will vary according to seasons. Both the ambient air temperature, and the inlet water temperature will affect the recovery rate.
(For sizing and advice on YOUR projects please call
Performance @ 25oC ambient air temp
| Model |
Heat Output To Water |
delivery 1st hr |
delivery continuous |
| 340-T (1x 340Lt storage tank/fan box) |
7kw |
449Lt |
134Lt/hr |
| 340-T3 (3x 340Lt storage tanks/fan boxes) |
21kw |
1347Lt |
402Lt/hr |
| 340-T4 (4x 340Lt storage tanks/fan boxes) |
28kw |
1796Lt |
536Lt/hr |
| 340-T5 (5x 340Lt storage tanks/fan boxes) |
35kw |
2245Lt |
670Lt/hr |
Performance @ 20oC ambient air temp
| Model |
Heat Output To Water |
delivery 1st hr |
delivery continuous |
| 340-T (1x 340Lt storage tank/fan box) |
6kw |
432Lt |
117Lt/hr |
| 340-T3 (3x 340Lt storage tanks/fan boxes) |
18kw |
1296Lt |
351Lt/hr |
| 340-T4 (4x 340Lt storage tanks/fan boxes) |
24kw |
1728Lt |
468Lt/hr |
| 340-T5 (5x 340Lt storage tanks/fan boxes) |
30kw |
2160Lt |
585Lt/hr |
Performance @ 15 oC ambient air temp
| Model |
Heat Output To Water |
delivery 1st hr |
delivery continuous |
| 340-T (1x 340Lt storage tank/fan box) |
5kw |
413Lt |
98Lt/hr |
| 340-T3 (3x 340Lt storage tanks/fan boxes) |
15kw |
1239Lt |
294Lt/hr |
| 340-T4 (4x 340Lt storage tanks/fan boxes) |
20kw |
1652Lt |
392Lt/hr |
| 340-T5 (5x 340Lt storage tanks/fan boxes) |
26kw |
2065Lt |
490Lt/hr |
|
|